Home Accuenergy Conzerv Crompton Digital-Switchboard Meters To Go Texmate Meters Utility Meters Watthour Meters Wilbac Meters . Alternatives For: Analogic Digitec EIL KEP Modutec Newport Precision Digital Red Lion Simpson Westcon . Current Transformers Switches-Disconnect Switches-Instrument Temp Sensors Transducers Ordering Info Order via Email Order Fax Quotation Fax
| |
Maximum Demand Indicator from Crompton.
Maximum Demand Indicator,
for the measurement of fundamental electrical
parameters, integrating high accuracy
measurement technology with the simplicity
and visibility of a single display system.
Got Questions? Call or email.
|
Integra 523 Measures A, A Demand V,L-L
and
Max Demand.
Integra 524 Measures A, A Demand V,L-L,
V, L-N and Max Demand
Distribution pillars, Feeder
panels & switchboards,
Low voltage
switchgear
Process
control and monitoring,
Motor
control centers
Energy
monitoring,
Any
application requiring Maximum Demand measurements.
|
Build the model number by following this
example.
Description: Meter +System+ W
Volts In+ Current In+ Aux+ Options
|
Model |
Circuit Description |
Order Number |
Price |
|
510 |
Three Phase, 3 Wire. A, V L-L, Hz (7 Measurements), Input
380-480V, 5 A |
244-513W-38LS |
166.40 |
|
510 |
Three Phase, 4 Wire. A, V L-N, Hz (7 Measurements), Input
380-480V, 5A |
244-514W-38LS |
176.80 |
|
520
|
Three Phase, 3W. A,
A Demand, A Max Demand, V L-L(12 Measurements)
Input 380-480V, 5A
|
244-523W-38LS |
210.00 |
|
520 |
Three Phase, 4 Wire. A, A Demand, A Max Demand, V L-L, V
L-N(15 Measurements), Input 380-480V, 5A |
244-524W-38LS |
210.00 |
|
530 |
Three Phase, 3 Wire - As 523 but with one output relay.
Input 380-480V, 5 A |
244-533W-38LS |
210.00 |
|
530 |
Three Phase, 4 Wire - As 524 but with one output relay.
Input 380-480V, 5A |
244-534W-38LS |
210.00 |
|
540 |
Three Phase, 3 Wire - As 523 but with two output relays.
Input 380-480V, 5A |
244-543W-38LS |
210.00 |
|
540 |
Three Phase, 4 Wire - As 524 but with two output relays.
Input 380-480V, 5A |
244-544W-38LS |
210.00 |
|
|
Self powered |
SP |
|
|
|
Auxiliary Powered 100-120V |
-10 |
|
|
|
190-240V |
-19 |
|
|
|
380-480V |
-38 |
|
|
|
One Demand Relay for 520 |
244-53S |
20.88 |
|
|
Two Demand Relay for 530 |
244-54S |
22.88 |
Benefits
Totally new
look MDI, 10
measurements in one unit,
Programmable C.T. ratios
Programmable time period, Readable in
bright sunlight, Replaces 3 combined MDI &
1 Voltmeter
Simple to
use, Measures
down to 2.5% of nominal input, overload capability
Features
High
contrast LCD, Large
characters, Standard 96
x 96mm DIN case
Self
powered or Auxiliary powered, Average
sensing, Password
protected
Reset can
be disabled, Two button
operation, Designed to
meet world-wide standard
approvals for safety and performance, EMC and LVD.
Input Specification
System:
Three phase
- three wire, Model 244-523. Three phase - four wire, Model 244-524
Voltage:
100-120V
L-L,190-240V L-L, 380-480V L-L
Current:
5 amps
(Standard) or 1 amp (Optional) Maximum C.T. ratio 8000:5A or 8000:1A
Measuring Range:
Current 2.5 - 120% Current Demand 2.5 - 120% Voltage (Auxiliary Powered)
2.5 - 120% Voltage (Self Powered) 75 - 125% of 115, 230
or 460V
Frequency:
45 to 66Hz
Demand Integration Period:
8, 15, 30 & 60 minutes
Burden:
Voltage:
Each line
0.2VA approx.
Current:
Each phase
0.6VA approx.
Overload Capability:
Continuous:
120% of
nominal (600V Max)
Short Duration:
2 x nominal
for one second
Repeated 10 times at 10 second intervals.
Current:
Continuous:
120% of
nominal
Short Duration:
20 x
nominal/1second Repeated 5 times at 5 minute intervals
10 x
nominal for 3 seconds Repeated 5 times at 5 minute intervals 5 x nominal
for 5seconds Repeated 5 times at 5 minute intervals
Auxiliary Supply
A.C. voltage:
100 - 120V 190 - 240V 380 - 480V -10% of lower nominal +20% of upper nominal
Burden 3VA approx.
Enclosure:
Size:
96 x 96 mm
DIN
Material:
Flame
retardant to UL94V-0/V-2
Terminals:
M3.5
captive screw & clamp
Accuracy Class
Voltage:
+1.5% of
nominal
Current:
+1.5% of
nominal
Current Demand:
3% of
nominal
Climatic
Temperature:
Operating
-10 to +70°C Storage -20 to +80°C Calibration 23°C
Temp Coeff:
±0.013%/°C
(typical)
Humidity:
95% RH non
condensing
Isolation:
2.2kV RMS
50Hz for 1 minute
Surge Voltage
Test:
IEC 801-5
High Frequency Disturbance:
4.2kV peak
IEC 255
Display
High
contrast LCD & Annunciation Characters
10.5mm high 3 lines of
data,
4 digits per line 4 digit
resolution with a floating decimal point for each value
All
parameters available via single button operation cascading through 4 screens
Comprehensive set-up facility via two buttons Update time
7.5 seconds approx. for
A & V, 1/8 of demand integration time for current demand.
|