Home Accuenergy Conzerv Crompton Digital-Switchboard Meters To Go Texmate Meters Utility Meters Watthour Meters Wilbac Meters . Alternatives For: Analogic Digitec EIL KEP Modutec Newport Precision Digital Red Lion Simpson Westcon . Current Transformers Switches-Disconnect Switches-Instrument Temp Sensors Transducers Ordering Info Order via Email Order Fax Quotation Fax
| |
Three Phase Digital Panel
Meter, DIN Style case.
Integra1530 Digital Three
phase Meter
Measures 23 Parameters.
Integra 1530 also features Large Red LEDs for easy viewing Tactile feedback keys for positive
user interface User programmable screen for custom
applications.
 Configuration Software |
Applications Include
Low voltage Switchgear and distribution
Process Control Monitoring Energy
and Building Management Systems Generator sets
Self contained.
Displayed Parameters Screen:
1. User Selectable
2. System voltage, avg. current, total
power
3. Voltage per phase L-N,
4. Voltage per phase to phase
5. Current per phase
6. System neutral current, frequency & PF
7. Power - kW (Active) & VAr (Reactive),
kVA (Apparent)
8. kWh (Active energy)
9. kVAr.h (Reactive energy)
10. Demand A & kW
11. Maximum demand A & kW
|
Build the model number by following this
example.
Description: Meter +Input +Aux +Comm +Output
+Options
| Code |
Description |
Price |
| K |
Single Phase |
$ 560.00 |
| M |
3 phase , 3 wire, unbalanced 2 elements |
$ 560.00 |
| W |
3 phase , 4 wire, unbalanced 2 elements |
$ 560.00 |
| |
Measured Input Description |
|
| QL |
69VAC, L-N 5A |
N/C |
| PN |
110VAC, L-N 5A |
N/C |
| QP |
115VAC, L-N 5A |
N/C |
| QQ |
120VAC, L-N 5A |
N/C |
| VQ |
220VAC, L-N 5A |
N/C |
| VR |
230VAC, L-N 5A |
N/C |
| QS |
240VAC, L-N 5A |
N/C |
| QY |
277VAC, L-N, 5A |
N/C |
| QP |
110VAC L-L, 5 A |
N/C |
| PQ |
120VAC L-L, 5 A |
N/C |
| QR |
208VAC L-L, 5 A |
N/C |
| QX |
380VAC L-L, 5 A |
N/C |
| QT |
480VAC L-L, 5 A |
|
| |
Auxiliary Power |
|
| HG |
120VAC 50-60Hz |
N/C |
| NC |
230VAC 50-60Hz |
|
| BD |
24VDC |
$ 50.00 |
| NR |
48VDC |
$ 50.00 |
| |
Communications Optional |
|
| RS |
RS 485 Modbus RTU protocol* |
$ 215.00 |
| |
Pulsed Outputs Optional |
|
| P1 |
One pulsed output kW.h |
$ 90.00 |
| |
Options |
|
| TC |
Hinged Cover |
$ 75.00 |
| MG |
Panel Gasket |
$ 2.50 |
Specification
Input
Voltage:
57.7, 63.5, 69.3, 110, 115,
120, 220, 230, 240, 254, 277V, 346 L/N
100, 110, 120, 208, 380, 400,
415, 440 480V L/L Measuring Range 10 - 100% Range 5 - 120%
Current:
5 amps (Standard) or 1 amp (Optional) Measuring Range 10 - 100%
Range 5 - 120%
Maximum C.T. ratio 4000:5A or 4000:1A
Frequency:
45 to 65Hz
Power Factor:
Range of use 0.5 Lag - 1 -
0.8 Lead
Overloads
Voltage:
2 x for 1 second (x10) at 10
second intervals Max. terminal voltage 1.2 times normal
Current:
20 x for 1 second (x5) at 5
minute intervals Max. continuous terminal current 1.2 times
nominal
Burden:
Voltage:
Each line <0.2VA
Current:
Each
phase <0.6VA
Isolation Input to Digital O/P.
= 2.2kV
Input to Pulsed O/P.
= 2.2kV
Accuracy Class
Voltage:
+0.4% of reading ±0.1% of
range
Current:
+0.4% of reading ±0.1% of
range Neutral +4% of range
Power:
kW kVA: +0.9 of reading
+0.1% of range kVAr: +1.9% of reading ±0.1% of range
Energy:
kW.h 1% IEC 1036 (PF
0.8-1-0.8) kVAr.h 2% IEC1036 (PF 0.8-1-0.8)
Frequency:
+0.15% of mid frequency
Phase Angle/
Power Factor:
1% of unity
Climatic
Temperature:
Operating 0 to 50°C Storage
-20 to +70°C Calibration 23°C
Temp
Coeff:
±0.013%/°C (typical)
Humidity:
95% RH non condensing
Auxiliary Supply
A.C.
voltage:
115 or 230V a.c.. +10%
Burden 6VA
D.C.
voltage:
12, 24, 30 & 48V d.c.
Approvals
Production:
ISO 9001 certificate no.
FM21540
Safety:
IEC 1010/BSEN 61010-1,
Installation category II pollution degree 2 600V RMS
Enclosure:
IP54 BSEN60529, IEC 529,
BS5490,
EMC:
Emissions
BSEN50081/1 Immunity BSEN50082/2
Test Method:
Measuring circuit BSEN
60688, IEC688 BSEN 61036, IEC 1036 (kWh functionality)
Outputs (optional)
Digital:
Ports: 1 off RS485 Modbus‚ RTU Protocol 2
wire, half duplex, Screw clamp terminals
Pulsed Type: Type
Import Energy
1 - Relay output SPNO 100V
d.c. 0.5A
|