Home Accuenergy Conzerv Crompton Hialeah Meter Texmate Meters Wilbac Meters . Digital Switchboard Electric Meter Energy Meters Revenue Grade Smart Meters Surplus Watthour Meters . Accessories: Current Transformers Potential Transformer Switch-Disconnect Switch-Instrument Temp Sensors Transducers Ordering Info Order via Email Order Fax Quotation Fax
| |
|
Power Meter,
Internet
Connection, select 5 Amp or 1 Amp Input.
Optional module
allows Emails
current-alarm
conditions.
Standard
TCP/IP browser protocol. |
Acuvim-II fits in ANSI or 96MM DIN
Cutout |
 |
|
The Acuvim II,
an inexpensive high-end multifunction power meter with multiple
communication schemes and ports includes RS485 Modbus as
standard Optional modules for: I/O, digital and analog,
Profibus-DP, Ethernet.
No special
software required, uses Internal web browsing software. Collects
data, communicates remotely.
Fits both ANSI and 96mm DIN cutouts.
3 Phase digital switchboard meter $495.00
optional modules listed below
|
|
Optional
Modules for Analog and Digital I/O, PROFIBUS-DP, Ethernet, Web based
Email.
Digital Switchboard Meter
connects to the internet
in a heartbeat.
No software required,
just an IP address and you are talking to your meter from any lap
or desk top for $675.00. |
|
Model |
Input |
Supply |
Price |
|
Acuvim-II |
5 Amp Input |
AC/DC |
$ 495.00 |
|
Acuvim-II |
5 Amp Input |
24VDC |
$ 570.00 |
|
Acuvim-II |
1 Amp Input |
AC/DC |
$ 525.00 |
|
AcuvimIIR5 |
5 Amp Input |
AC/DC |
$ 695.00 |
|
|
|
UL Certified,
True-RMS Measuring Parameter
4-Quadrant Energy
Power Quality Analysis
|
Over Limit Alarm
Multi Comm. Ports (Ethernet, Modbus)
Web Server and Email Sending
Switch Status Monitoring
Remote Switch Controlling
Acuvim
II Installation Manual
Acuvim II
Brochure
Modbus Map.
|
Features:
 | Panel Metering
 |
Voltage, Current, Power, Reactive
Power, Apparent Power,
|
Frequency, Power Factor, Energy, Reactive Energy, Demand
|
 | Panel Monitoring
 | Power Quality: |
 | Voltage Harmonics 2nd to 31st and THD |
 | Current Harmonics 2nd to 31st and THD |
 | Voltage Crest Factor |
 | THFF (TIF) |
 | Current K Factor |
 | Voltage Unbalance Factor U_unbl |
 | Current Unbalance Factor U_unbl |
 | Max/Min Statistics with Time Stamps |
 | Switch Status |
|
 | Remote Control |
 | Alarms
 | The limits of the less than 9 indicated parameters can be set
|
with a specified, time interval. If any input of the 9 indicated
parameters is over or under its setting limit with persisting time
over specified time interval, the event will be recorded with time
stamps and trigger the Alarm DO output. The 9 indicated parameters
can be any of the following:
F, V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg, I1, I2, I3, Iavg, In,
P1, P2, P3, Psum, Q1, Q2, Q3, Qsum, S1, S2, S3, Ssum, PF1, PF2, PF3,
PF, U_unbl, I_unbl, Dmd_P, Dmd_Q, Dmd_S
|
 | Ethernet or Profibus Communication
 | 10M/100M self-adaptable, RJ45 Jack Modbus-TCP/IP Protocol |
 | HTTP Web page browse Email sending on time interval or on event
|
 | Profibus-DP/V0 Input Byte (typical): 32 byte Output Byte (typical):
|
 | 32 Byte EN50170 vol.2 compliance |
 | Profibus slave mode, baud rate self-adaptable up to 12M |
|
 | Fexible I/O module
 | Digital Input, Digital Output, Relay Output, |
 | Analog Input, Analog Output, Pulse Output |
|
 | 2 Communication Ports |
| Function |
|
Parameter |
|
Phase Voltage |
V1, 2, 3 |
| REAL TIME |
Line Voltage |
V1-2, 2-3, 3-1 |
| METERING |
Current |
I1, 2, 3,L-N |
|
Power
(Instant KW) |
P1, 2, 3, sum |
|
Reactive Power |
Q1, 2, 3, sum |
|
Apparent Power |
Ssum |
|
Power Factor |
PF1, F2, F3, F |
| ENERGY DEMAND |
ENERGY
(KWh) |
Ep_iimp, p_exp, |
|
REACTIVE ENERGY |
Eq_imp, q_exp |
|
Apparent Energy |
Dmd_I1,DDmd_I2 md_II3 |
|
POWER DEMAND |
Dmd_Psum, md_QQsum |
|
Voltage Imbalance Factor |
V_unbl |
|
Current Imbalance |
I_unbl |
| POWER QUALITY |
Voltage THD |
THD_V1, THD_V2, THD_V3, |
|
Current THD |
THD_I1, THD_I2, THD_I3 |
|
Individual Harmonics |
2 nd 31 th (Current and Voltage) |
|
Voltage Crest Facctor |
Crest Factor |
|
TIF |
THFF |
|
Current K Factor |
K Factor |
| STATISTICS |
Max with Time Stamp |
|
|
Min with Time Stamp |
|
| ALARM |
Over Under Limit Alarm |
|
| COMMUNICATION |
RS-4485 MODBUS ®-RTU Protocol |
| TIME |
Real Time Clock |
|
|
Switch Status (DI) |
Digital input wet |
|
Power Supply for DI |
24VDC |
|
Relay Output (RO) |
NO, Form A |
| I/O OPTIONAL |
Digital Output (DO) |
Photo -MOS |
| MODULES |
Pulse Output (PO) |
By using DO |
|
Analog Inpit (AI) |
0(4)-20mA, 0(1)-5V |
|
Analog Output (AO) |
0(4)-20mA, 0(1)-5V |
| OPTIONAL |
Ethernet |
10M/100M Modbus TCP,HTTP |
| COMMUNICATIONS |
|
Web page Email |
|
Profibus-DP |
Profibus-DP/VO |
| |
|
|
|
|
|
|
|
|
I/O MODULE OPTION
I/O Outputs Details |
| Module Name |
Price |
Digital Input |
Power
Supply
|
Digital
Output
|
Relay Output |
Analog Input |
Analog Output |
|
AXM101 |
$75.00 |
6 |
1 |
|
2 |
|
|
|
AXM102 |
$80.00 |
4 |
|
2 |
|
|
2 |
|
AXM103 |
$90.00 |
4 |
|
|
2 |
2 |
|
|
COMMUNICATION MODULE OPTIONS |
| Module Name |
Specifications |
|
|
| ETHERNET |
10M/ 100M Self Adaptable RJ45 jack
Ethernet Module Data |
|
AXM-NET |
Modbus TCP/IP Protocol |
|
|
|
| $130.00 |
HTTP Web page Browse |
|
|
|
|
Email sending on time internal or event |
|
|
| PROFIBUS |
Profibus-DP/VO Input Byte typical 32byte |
|
|
|
$145.00 |
Output Byte typical 32 byte ENS0170 vol 2 compliance |
| |
Profibus slave mode baud rate self- adaptable up to 12 Meg. |
|